Ul Standards; Area Of Use; Wire The Main Circuit Terminal Block - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

5.3

UL Standards

The UL/cUL Mark indicates that this product satisfies stringent safety standards. This mark appears on products in the
United States and Canada. It shows UL approval, indicating that it has been determined that the product complies
with safety standards after undergoing strict inspection and assessment.
You must use UL Listed or UL Recognized parts for all primary components that are built into electrical equipment
that has UL approval.
This product has been tested in accordance with UL standard UL61800-5-1, and has been verified to be in compliance
with UL standards.
Machines and devices integrated with this product must satisfy the following conditions for compliance with UL
standards.

Area of Use

Install this product in a location with Overvoltage Category III and pollution degree 2 or less as specified in
UL61800-5-1.
Ambient Temperature Setting
Maintain the ambient temperature within the following ranges according to the enclosure type.
• IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
• IP00/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)
• IP20/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)
• IP55/UL Type 12 Heatsink External Mounting; front side: -10 °C to +50 °C (14 °F to 122 °F)
• IP55/UL Type 12 Heatsink External Mounting; back side: -10 °C to +40 °C (14 °F to 104 °F)

Wire the Main Circuit Terminal Block

Wire the main circuit terminal block correctly as specified by the instructions in the manual.
To comply with UL standards on drive models 2257 to 2415, 4208 to 4720, and T208 to T720, use UL-approved
closed-loop crimp terminals. Use the tools recommend by the terminal manufacturer to crimp the closed-loop crimp
terminal. Refer to
Closed-Loop Crimp Terminals on page 285
crimp terminals.
To select the correct wire gauge, refer to
278.
Notes on Wiring the Main Circuit Terminal Block
Read these notes before you wire the main circuit terminal block.
• Use UL-Listed, vinyl-coated insulated copper wires for operation with a continuous maximum permitted
temperature of 75 °C at 600 V.
• Remove all unwanted objects that are near the terminal block connections.
• Remove the insulation from the connection wires to the wire stripping lengths shown in the manual.
• Do not use bent or crushed wires. Remove the damaged end of the wire before you use it. Incorrect connections can
cause death or serious injury from fire.
• Do not solder stranded wire. Soldered wire connections can become loose over time and cause unsatisfactory drive
performance.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Figure 5.20 UL/cUL Mark
for more information about UL Listed closed-loop
Three-Phase 200 V Class on page 274

5.3 UL Standards

and
Three-Phase 400 V Class on page
5
271