Factory-Recommended Branch Circuit Protection For Ul Listing - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

3.15
Factory-Recommended Branch Circuit Protection for UL
Listing
WARNING! Electrical Shock Hazard. After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.

Factory-Recommended Branch Circuit Protection for UL Listing

Use branch circuit protection to protect against short circuits and to maintain compliance with UL 508C. Yaskawa
recommends fuses for semiconductor protection. Refer to
Class on page
148, and
6-Phase/12-Pulse 400 V Class on page 149
short circuit protection devices.
WARNING! Electrical Shock Hazard. After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.
• 200 V Class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than 100,000
RMS and not more than 240 Vac when there is a short circuit in the power supply.
• 400 V Class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than 100,000
RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric (NEC), the Canadian Electric Code, Part I (CEC), and
local codes.
Three-Phase 200 V Class
Drive Mounted without
Supplemental Enclosure
(Using UL Type 1 Kit)
Semiconductor
Drive Model
Fuse
Manufacturer:
EATON/
Bussmann
(Permitted Only
in UL Type 1
Kit)
*1
2004
N/A
*1
2006
N/A
*1
2008
N/A
*1
2010
N/A
*1
2012
N/A
*1
2018
N/A
*1
2021
N/A
*1
2030
N/A
*1
2042
N/A
*1
2056
N/A
YASKAWA SIEPC71061737D GA800 Drive Technical Reference

3.15 Factory-Recommended Branch Circuit Protection for UL Listing

Table 3.21 Required Short Circuit Protection
Any Size Protected Enclosure
(Ventilated/Non-Ventilated)
Class CC, J, or
Semiconductor
T Fuse
Fuse
Maximum
Manufacturer:
Amps
EATON/
Bussmann
(A)
(Drive and
(Permitted in
Fuses in Same
Same or
Enclosure
Separate
Only)
Enclosure)
7
FWH-45B
10
FWH-45B
12
FWH-45B
15
FWH-45B
FWH-50B, FWH-
20
80B
FWH-80B, FWH-
30
100B
FWH-80B, FWH-
35
100B
FWH-100B,
50
FWH-125B
70
FWH-150B
90
FWH-200B
Three-Phase 200 V Class on page
for the recommendation fuses and the alternative
Drive Mounted in Supplemental Enclosure
Restricted Size Protected Enclosure
Class CC, J, or
These Devices Permitted in Same or Separate Enclosure
T Fuse
Maximum
Class CC, J, or
Amps
T Fuse
(A)
Maximum
(Permitted in
Amps
Same or
(A)
Separate
Enclosure)
*2
7
*2
10
*2
12
*2
15
*2
20
*2
30
*2
35
*2
50
*2
70
*2
90
147,
Three-Phase 400 V
(Ventilated Only)
Class RK1 or
MCCB
RK5 Fuse
Enclosure
Maximum
Maximum
Amps
Amps
(A)
(A)
15
7
15
10
15
12
15
15
20
20
35
30
40
35
60
50
80
70
110
90
3
Minimum
Volume
(in
3
)
4195
4195
4195
4195
4195
4195
4195
4195
4195
4195
147