Install a Braking Unit Connection: CDBR-Type

To install a CDBR-type braking unit, connect terminal +3 on the drive to terminal + on the braking unit, and connect
terminal - on the drive to terminal - on the braking unit. Terminal +2 on the drive is not necessary for CDBR-type
braking unit connections.
Set L8-55 = 0 [Internal DB TransistorProtection = Disable].
Note:
• To install a CDBR-type braking unit to the drive models 2004 to 2138 and 4002 to 4168 that have a built-in braking transistor, connect
drive terminal B1 to terminal + on the braking unit.
• A junction terminal is necessary to connect a braking unit (CDBR-series) to drive models 2169, 2211, 4140, 4168, T140, and T168. To wire
the braking unit, install a junction terminal that can connect to wires in the range specified for the drive, peripheral devices, and options.
This table shows recommended junction terminals. Contact Yaskawa or your nearest sales representative for more information about
selection and installation of the junction terminal.
Drive Model
2169, 4140, 4168, T140, T168
*1
The junction terminal must have two or more poles.
Figure 3.72 Install a Braking Unit: CDBR-Type/Braking Resistor Unit: LKEB-Type
Braking Unit Connection Wire Gauge (CDBR-Type)
To comply with IP20 when you connect the braking unit (CDBR-type) to drive models 2257 to 2415, 4208 to 4720, or
T208 to T720, refer to
Table
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Figure 3.71 Install a Braking Resistor Unit: LKEB-Type
2211
3.18,
Table
3.19, and
Table 3.20
3.9 Braking Resistor Installation
Junction Terminal Model
Manufacturer: Mibu Denki Industrial Co., Ltd.
*1
DTK-200N × 2P
*1
DTK-300N × 2P
to select the wires.