C.1 UL Standards
C.1 UL Standards

UL Standards Compliance

The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing
and evaluation, and determined that their stringent standards for product safety have been met. For a product to receive
UL certification, all components inside that product must also receive UL certification.
Figure C.1
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions
described below must be met to maintain compliance when using this drive in combination with other equipment:
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
Ambient Temperature
Install the drive in an environment with an ambient temperature of -10
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection on a secondary circuit of a 6-
Phase/12-Pulse transformer to maintain standards compliance.
Refer to local codes for proper Branch Circuit Protection on the primary circuit of a 6-Phase/12-Pulse transformer.
The maximum Time Delay fuse is 175% of drive input current rating listed in
class fuse.
A Class L fuse is also approved for this rating at 175% drive input current listed in
Table C.1 Factory Recommended A1000 AC Drive Branch Circuit Protection
Model
Nominal Output Power
CIMR-A
4T0058
4T0072
4T0088
4T0103
4T0139
4T0165
4T0208
4T0250
4T0296
4T0362
4T0414
4T0515
4T0675
<1> This amp rating is 1/2 rated current because the 3-Phase current is split between 6 input phases for the 6-Phase/12-Pulse A1000 drive. Use this
amp rating to select input wiring size as recommended in
64
Figure C.1 UL/cUL Mark
kW (HP)
30 (40)
37 (50)
45 (60)
55 (75)
75 (100)
90 (125)
110 (150)
132 (200)
160 (250)
185 (300)
220 (350)
250 (400)
355 (550)
Table
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
C to 40
C (Flange Type Enclosure).
°
°
Table
AC Drive
Input Amps/Phase
<1>
29
35.5
43
52.5
71
85
103.5
124
150
173
205
232.5
328.5
3.2.
C.1. This covers any Class CC, J or T
Table
C.1.
Time-Delay Fuse Class J or T
Rating Amps
40
50
60
75
90
110
150
175
225
225
275
350
450