3.15 Branch Circuit Protection

3.15

Branch Circuit Protection

Factory-Recommended Branch Circuit Protection for UL Listing

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with
UL 508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also
listed. Maximum Time Delay fuse is 175% of drive full load output amps (FLA). This covers any Class CC, J, or T
class fuse. Refer to
200 V Class on page 124
WARNING! Electrical Shock Hazard. After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.
• 200 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than 100,000
RMS and not more than 240 Vac when there is a short circuit in the power supply.
• 400 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than 100,000
RMS and not more than 480 Vac when there is a short circuit in the power supply.
The built-in short circuit protection of the drive does not provide branch circuit protection. The user must provide
branch circuit protection as specified by the National Electric Code (NEC), the Canadian Electric Code, Part I (CEC),
and local codes.
200 V Class
Drive Model
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
2169
2211
124
and
400 V Class on page 125
Table 3.19 Factory Recommended Fuses for 200 V Class
Semiconductor Fuse
Manufacturer: EATON/Bussmann
FWH-45B
FWH-45B
FWH-45B
FWH-45B
FWH-50B
FWH-80B
FWH-80B
FWH-100B
FWH-80B
FWH-100B
FWH-125B
FWH-150B
FWH-200B
FWH-225A
FWH-225A
FWH-250A
FWH-225A
FWH-250A
FWH-275A
FWH-300A
FWH-275A
FWH-350A
FWH-325A
FWH-450A
for the recommended fuses.
*2
*2
*2
*2
*2
*2
*2
*2
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Alternate Time-Delay
*1
Class CC, J, or T
Maximum Amp Rating
(Maximum SCCR (kA))
6 (65)
10 (65)
12 (65)
15 (65)
20 (65)
30 (65)
35 (65)
50 (100)
70 (100)
90 (100)
110 (100)
125 (100)
175 (100)
225 (100)
250 (100)
350 (100)

Advertisement