92
Name
Warning
Indicates that the Inverter detected a
warning.
0: Normal
1: Warning detected.
Faulted
Indicates that the Inverter detected a
fault.
0: Normal
1: Fault detected.
Terminal
Indicates the input status of Inverter
S1
multi-function input terminal S1. When
using this terminal as a general-purpose
DI terminal, always set Inverter constant
n050 to 28.
0: Terminal S1 OFF
1: Terminal S1 ON
Terminal
Indicates the input status of Inverter
S2
multi-function input terminal S2. When
using this terminal as a general-purpose
DI terminal, always set Inverter constant
n051 to 28.
0: Terminal S2 OFF
1: Terminal S2 ON
Terminal
Indicates the input status of Inverter
S3
multi-function input terminal S3. When
using this terminal as a general-purpose
DI terminal, always set Inverter constant
n052 to 28.
0: Terminal S3 OFF
1: Terminal S3 ON