YASKAWA Varispeed V7 Instruction Manual page 183

Compact general-purpose inverter
Table of Contents

Advertisement

PID Offset Adjustment (n133)
Constant
No.
n133
Constant n133 adjusts the PID control offset.
If both the target value and the feedback values are zero, adjust n133 so
that the Inverter output frequency is zero.
Primary Delay Time Constant for PID Output (n135)
Constant
No.
n135
Constant n135 is the low-pass filter setting for PID control outputs.
There is normally no need to change the setting.
If the viscous friction of the mechanical system is high or if the rigidity
is low causing the mechanical system to resonate, increase the setting so
that it is higher than the resonance frequency period.
PID Output Gain (n163)
Constant
No.
n163
Constant n163 adjusts the output gain.
PID Feedback Gain (n129)
Constant
No.
n129
Constant n129 is the gain that adjusts the feedback value.
182
Name
PID Offset Adjustment
Name
Primary Delay Time
Constant for PID Output
Name
PID Output Gain
Name
PID Feedback Gain
Unit
Setting
Range
%
-100 to 100
Unit
Setting
Range
0.1 s
0.0 to 10.0
Unit
Setting
Range
Multi-
0.0 to 25.0
ples
Unit
Setting
Range
Multi-
0.00 to 10.00
ples
Factory
Setting
0
Factory
Setting
0.0
Factory
Setting
1.0
Factory
Setting
1.00