YASKAWA Varispeed V7 Instruction Manual page 144

Compact general-purpose inverter
Table of Contents

Advertisement

Using Two Acceleration/Deceleration Times
FORWARD (REVERSE)
FUN command
Multi-Step
Speed Reference
Accel/Decel
Time Selection
(Terminals S1 to S7) (See note.)
* When deceleration to a stop is selected (n005 = 0).
By setting a multi-function input selection (either of n050 to n056) to 11
(acceleration/deceleration time select), the acceleration/deceleration
time is selected by turning ON/OFF the acceleration/deceleration time
selection terminals (terminals S1 to S7).
Note: Input terminals S5 through S7 can be used only from DeviceNet com-
munications. There are no corresponding external input terminals.
At OFF: n019 (Acceleration Time 1)
n020 (Deceleration Time 1)
At ON: n021 (Acceleration Time 2)
n022 (Deceleration Time 2)
No.
n019
Acceleration Time 1
n020
Deceleration Time 1
n021
Acceleration Time 2
n022
Deceleration Time 2
Decel
Time 1
Accel
(n020)
Time 1
(n019)
Name
7. Programming Features
Decel
Accel
Time 2*
Time 2
(n022)
(n021)
Time
ON
ON
ON
Unit
Setting
Range
Refer to
Refer to
n018
n018
setting
setting
Decel
Time 1*
(n020)
Factory
Setting
10.0 s
10.0 s
10.0 s
10.0 s
143