YASKAWA Varispeed V7 Instruction Manual page 118

Compact general-purpose inverter
Table of Contents

Advertisement

Error
Contents
Code
1FFF
Vendor spe-
cific error
20FF
Invalid param-
eter
MEMOBUS I/O Instance Error Table
The following errors can occur when using the MEMOBUS I/O
Instance to set or reference Inverter constants.
Error
Contents
Code
01 Hex
Function
code error
02 Hex
Improper
register
number
6. Operating with DeviceNet Communications
Cause
• Attempted to
change an
Inverter con-
stant that can-
not be changed
while the
Inverter is run-
ning.
• Attempted to
change an
Inverter con-
stant to a value
outside of the
setting range.
Attempted to
change to a data
value outside of
the setting range.
A function code other than 00 Hex, 03
Hex, or 10 Hex was sent from the mas-
ter.
• No register number has been regis-
tered to specify the register to be
accessed.
• ENTER command 0900H was exe-
cuted for a write-only register.
Corrective Action
• Stop the
Inverter.
• Specify a value
that is within
the setting
range.
Specify a data val-
ue that is within
the setting range.
Cause