6. Operating with DeviceNet Communications
Data
Name
Byte 1,
Terminal
bit 5
MA*
Byte 1,
Terminal
bit 6
P1
Byte 1,
Terminal
bit 7
P2
Bytes
Frequency
2 and 3
Reference
Bytes
Accelera-
4 and 5
tion Time 1
Operates the Inverter's multi-function
output terminal MA. This function is en-
abled only when Inverter constant n057
is set to 18.
0: Terminal MA OFF
1: Terminal MA ON
Operates the Inverter's multi-function
output terminal P1. This function is en-
abled only when Inverter constant n058
is set to 18.
0: Terminal P1 OFF
1: Terminal P1 ON
Operates the Inverter's multi-function
output terminal P2. This function is en-
abled only when Inverter constant n059
is set to 18.
0: Terminal P2 OFF
1: Terminal P2 ON
Sets the Inverter's speed reference.
This setting is the same as the speed
reference in the V7 standard control I/O
instance. The units depend on the set-
ting in Inverter constant n035.
Sets the Inverter's acceleration time.
The units depend on the setting in
Inverter constant n018. (The factory set-
ting is for units of 0.1 s.) The value set
here is recorded in EEPROM. The units
are not affected by the time scale (TS)
setting.