YASKAWA Varispeed V7 Instruction Manual page 198

Compact general-purpose inverter
Table of Contents

Advertisement

n035 Settings
Setting
0
• Setting unit: 0.01 Hz (less than 100 Hz), 0.1 Hz (100
Hz and more)
• Setting range
min {Fmax (n011) × Frequency Reference Lower Limit
(n034) to Fmax (n011) × Frequency Reference Upper
Limit (n033), 400 Hz}
1
• Setting in units of 0.1%: 100.0%/Fmax (n011)
• Setting range
Min. {Frequency Reference Lower Limit (n034) to Fre-
quency Reference Upper Limit (n033), (400 Hz ÷
Fmax. (n011)) 100%}
Max. Upper Limit Value: Fmax. (n011) × Set value (%)
≤ 400 Hz
• Setting in units of 1 r/min: r/min=120 × Frequency ref-
2 to 39
erence (Hz) ÷ n035 (Set the number of motor poles in
n035)
• Setting range
Min. {120 (Fmax (n011) Frequency Reference Lower
Limit (n034) ÷ n035 to 120 × (Fmax (n011) × Fre-
quency Reference Upper Limit (n033)) n035, 400 Hz ×
120 P, 9999r/min
• Max. Upper Limit Value: N × P ÷ 120 ≤ 400 Hz
40 to
• Set the display value at 100% of frequency reference
3999
(set value of Fmax (n011)) at 1st to 4th digits of n035.
In the 4th digit of n035, set the position of decimal
point.
In the 1st to 4th digits of n035, set a 3-digit figure
excluding the decimal point.
Example: To display 20.0 at 100% of frequency refer-
ence, set n035 to 1200.
• Setting range
Min. {Lower 3-digits of n035) × Frequency Reference
Lower Limit (n034) to (Lower 3-digits of n035) × Fre-
quency Reference Upper Limit (n033), 400 Hz (Lower
3-digits of n035) × Fmax (n011), 999}
Max. Upper Limit Value: (Set value ÷ (Lower 3 digits of
n035)) × Fmax(011) ≤ 400 Hz
Note: 1. The frequency reference constants and monitor display data for
Description
4th digit Position of decimal point
0
1
2
.
3
0.
7. Programming Features
.