Operating at Low Speed
By inputting a JOG command and then a FORWARD (REVERSE)
RUN command, operation is enabled at the jog frequency set in n032.
When multi-step speed references 1, 2, 3 or 4 are input simultaneously
with the JOG command, the JOG command has priority.
Constant No.
n032
n050 to n056
Note: Input terminals S1 to S7 can be used only from DeviceNet communica-
tions. There are no corresponding external input terminals.
Adjusting Speed Setting Signal
The relationship between the analog inputs and the frequency reference
can be set to provide the frequency reference as analog inputs to Digital
Operator terminals CN2-1, CN2-2, and CN2-3.
Frequency Reference
1. Analog Frequency Reference Gain (n068 for voltage input, n071 for
current input)
The frequency reference provided when the analog input is 10 V (or
20 mA) can be set in units of 1%. (Max. Output Frequency
n011=100%)
* Factory setting: 100%
2. Analog Frequency Reference Bias (n069 for voltage input, n072 for
current input)
The frequency reference provided when the analog input is 0 V
(4 mA or 0 mA) can be set in units of 1%. (Max. Output Frequency
n011=100%)
* Factory setting: 0%
Name
Jog Frequency
Jog References Set to 10 for any constant.
7. Programming Features
Setting
Factory setting: 180 r/min
( ) indicates the value when a current
reference input is selected.
141