Machine Configuration
Oil Pressure Protection Setpoint
Oil Pressure Protection:
Press <+> <-> To Change Setting
Possible values of [Input] are: Diff Xducer
Factory default is Diff Xducer.

Programmable Analog Output

Program Analog Output:
Press <+> <-> To Change Setting
Possible values of [Output] are: Not Used
Factory Default is % RLA.

Programmable Relay Outputs

The following represents three menu items and is repeated for [N] = 1, 2,
or 3.
Program Relay [N]:
Press <+> <-> To Change Setting
Possible values of [Relay] are: Not Used
Factory Default for [N] = 1 is MMR + MAR Alarm.
Current Transducer Setpoint
The following will only be displayed if starter type is set to "Stand Alone -
No Starter Module".
Current Xducer:
Press <+> <-> To Change Setting
Possible values for [Setting] are: Cutler Hammer, Other
Factory Default is "Cutler Hammer"
Note: Select "Cutler Hammer" if starter has an A-1 module, otherwise
select "Other".

Current Transducer at 100 RLA

The following will only be displayed if Current Transducer is set to
"Other".
Current Xducer at 100% RLA:
Press <+> <-> To Change Setting
Range of values is -10.0 to -5.0 VDC in increments of 0.1 VDC
Note: Calculate setpoint as follows:
Current Transducer at 100% RLA =
Diff Switch
% RLA
Comp Running
MMR Alarm
MAR Alarm
MMR + MAR Alarm Max Capacity
= 2 is Comp Running.
= 3 is Not Used.
(
Machine LRA
CT Span
[Input]
[Output]
% Cond Pres
Refrig Diff Pres
[Relay]
Limit Warning
Ice Making
Head Relief Request
Tracer Controlled
[Setting]
XX.X VDC
)
)
(
X
-10.0
CVRC-M-1D