Machine Configuration Group:
Menu Item
31
Printer Option
32
Duplex Control Module
(DCM) Option
33
IGV Output Type
34
Oil Pressure Protection
35
Programmable Analog
Output
36
Program Relay [N]
[N] = 1, 2 or 3
37
Current Transducer
38
Current Transducer at 100%
RLA (Displayed only if
Current Transducer is set to
"Other")
39
Outdoor Air Temp Sensor
(FastPak Air Cooled Only)
CVRC-M-1D
FastPak
"Settings Group" Menu Record
Choices
Installed, Not Installed
Installed, Not Installed
Stepper Motor, Pulsed
Xducer; Diff Switch
Not Used; % RLA; % Cond
Pres; Refrig Diff Pres
Not Used; Comp Running;
MMR Alarm; MAR Alarm;
MMR + MAR Alarm; Limit
Warning; Ice Making; Head
Relief Request; Tracer
Controlled; Max Capacity
Cuttler Hammer, Other
-10.0 to -5.0 VDC in 0.1 VDC
Increments
Installed, Not Installed
Default
Design/Actual
Not Installed
Not Installed
Stepper Motor
Xducer
% RLA
1 = MMR + MAR Alarm
2 = Comp Running
3 = Not Used
Cutler Hammer
-8.2 VDC
Installed
17