Surge Protection Enable; Under/Over Voltage Protection Enable; Phase Reversal Protection Enable - Trane CVRC-M-1D Manual

Table of Contents

Advertisement

CVRC-M-1D
Field Startup
Purge Low Chiller Sat. Cond. Liquid Temp Protection
Enable
The following screen shall be suppressed if the selected Purge
Control/Type is "Stand-Alone Purge".
Prg Low Liquid Temp Inhibit Enable:
Press <+> <- > to Change Setting
Possible values of [d/e] are: Disable; ROM Default. Enable.
Purge Low Chiller Sat. Cond. Temp Setpoint
Prg Low Liq Temp Inhibit Setpt:
Press <+> <- > to Change Setting
Range of values is 32 to 50° F (0.0 to 10.0° C) in increments of 1 or 0.1°
F or C depending on the Service Setup Screen XXX or XXX.X. Factory
default is 40° F (4.4° C). Does not display this menu item unless this
feature is enabled in the menu above.

Surge Protection Enable

The following is suppressed if FastPak starter type is set equal to "Stand
Alone - No Starter Module".
Help Note: This detects gas surge as seen through unit power.
Surge Protection:
Press <+> <- > to Change Setting
Possible values of [d/e] are: Disable, Factory default is Enable.

Under/Over Voltage Protection Enable

This screen is displaced only when line voltage sensing is installed.
Help Note: Set trip protection at ± of nominal voltage.
Under/Over Voltage Protection:
Press <+> <- > to Change Setting
Possible values of [d/e] are: Disable, Factory Default is Enable

Phase Reversal Protection Enable

The following is suppressed if starter type is set to AFD or if FastPak
starter type is set to "Stand Alone - No Starter Module".
Phase Reversal Protection:
Press <+> <- > to Change Setting
Possible values of [d/e] are: Disable; Factory Default is Enable
Help Note: otation must be cloc wise C from the Thrustbearing end.
[d/e]
XX.X F/C
[d/e]
[d/e]
[d/e]
59