Operator Settings

The Operator Settings Group sequence is as follows:
Report Heading
Chilled Water & Current Limit Setpts
Press <Next> <Previous> To Continue
Following proper password entry or suppression the remaining sequence
will follow:
If the Menu Settings Password is Enabled in the Service Setup Group,
following each setting group heading the following will be displayed:
Settings In This Menu Are [status]
Likewise, if the Menu Settings Password is Disabled in the Service Setup
Group, the above screen will be suppressed.
The possible values for status are "Locked" or "Unlocked". If the
password status is locked, the password message will be "Enter
Password to Unlock". The user will then depress
followed by the <Enter> key. The password keystrokes will be echoed to
the screen as a visual aide. The last six keystrokes represent the current
password and up to twenty keystrokes can be entered. An incorrect
password or the twenty-first keystroke will result in the password
message "Invalid Password".
If the password status is unlocked, the password message will be "Press
<Enter> to Lock". Pressing <Enter> locks the settings in ALL menus. If
the password is entered to unlock the settings, this unlocks the settings
in ALL menus.
Whenever a password is in use the "Press<+><-> to change setting"
message will suppressed on setpoint screens. Any attempt to change the
setting will result in the message "Setting is Locked". The password once
entered will remain valid until canceled.

Purge Operating Mode

Purge Operating Mode:
Press <+> <-> To Change Setting
Possible values of (mode) are: Stop, On, Adaptive, Factory Default is
Auto.
[passsword message]
-
-
-