Machine Configuration

Acceleration Timeout Action

The following is suppressed if starter type is set to "Stand Alone No Str
Module".
Acceleration Time Out Action:
Press <+> <-> To Change Setting
Possible values for action include: Transition, Factory default is Shutdown.
Shutdown will result in an MMR Diagnostic. Transition will result in an
IFW diagnostic.
Starter Type
Undefined
Variable Speed
Y-Delta
X-Line
Solid State
Auto-Transformer
Primary Reactor
AFDB
Solid State SMCDP
Motor Over Temperature Protection
Motor Temp Protection:
Press <+> < - > to Change Setting
Possible value of [input] are: 3 Winding Sensors
Factory default is 3 Winding Sensors

Motor Winding RTD Type

The following is suppressed if motor temp protection is set to "MTC
Switch".
Motor Winding RTD Type
Press <+> <-> To Change Setting
Possible values for type are: 100 Ohm at 32 °F (0 °C), Factory default is
75 Ohm at 75 °F (24 °C).

High Pressure Cutout Setting

High Pressure Cutout Setting
Press <+> <-> To Change Setting
The range of values will be (-5) - 500 PSIG in increments of 1 PSIG from
-5 to 5 PSIG and 5 PSIG increments from 5 to 500 PSIG. Factory default
is 15 PSIG for a standard unit and 25 PSIG for an ASME unit.
6.8948 kPa = 1 psi.
Help Note: This is the ressure imit lgorithm that will, in sequence,
Limit - Hold - Close vane opening.
Limit Loading - Hold Loading - Close orced nload
Recommended "Action" Value
Contact Factory
Shutdown
Transition
Shutdown
Shutdown
Transition
Transition
Shutdown
Shutdown
MTC Switch
XXXX PSIG
[Action]
[input]
[Type]
73