Clear Restart Inhibit Timer - Trane CVRC-M-1D Manual

Table of Contents

Advertisement

54
Basic Setups
Help Note:
This will print every time a diagnostic occurs.
Number of Pre-Diag Reports:
Press <+> <- > to Change Setting
Range of Values is 1 to 5 in increments of 1. Factory Default is 5 (5 =
Time Interval). XX is used for Trend Analysis it saves reports ahead of
the diagnostic.
Diagnostic Report Interval:
Press <+> <- > to Change Setting
Range of Values is 2 to 120 seconds in increments of 1 second. Factory
Default is 5 seconds.
Printer, Baud Rate:
Press <+> <- > to Change Setting
The choices for Status are:
300
1200
2400
Help Note: This information is set-up based on your particular printer.
Refer to Printer Manual.
Printer, Parity:
Press <+> <- > to Change Setting
The choices for Status are: None (Factory Default), Odd, Even.
Printer, Data Bits:
Press <+> <- > to Change Setting
The choices for Status are: 8 (Factory Default), 7.
Printer, Stop Bits:
Press <+> <- > to Change Setting
The choices for Status are: 1 (Factory Default), 2.
Printer Handshaking:
Press <+> <- > to Change Setting
The choices for Status are:
XON / XOFF (Factory Default)
DTR

Clear Restart Inhibit Timer

Clear the Restart Inhibit Timer
When <Enter > is pushed a 2 second message appears as shown below
and then returns to above screen.
Restart Inhibit Timer Has Been Cleared
xx sec
[Status]
4800
9600 (Factory Default)
19,200
[Status]
[Status]
[Status]
[Status]
RTS
None
Press <Enter> to
xx
CVRC-M-1D