Trane CVRC-M-1D Manual page 82

Table of Contents

Advertisement

82
Refrigerant Monitor Calibration
If the refrigerant monitor is unable to calibrate, the following item shall be
displayed.
Otherwise, continue with the following screens.
Refrigerant Zero Calibration
Press (Ent) (Cancel) (+) (-) To Continue
Starting The Calibration Procedure
This item shall be followed by one of the following two items.
(Enter) To Retry, (Cancel) To Exit
If the Enter key is pressed, the display shall return to the second menu
item above. If the Exit key is pressed, the display shall continue to the
next display.
Refrigerant Span Calibration
Refrigerant Span Calibration
(Enter) To Start, (Next) To Continue
If Next is pressed the following refrigerant span calibration screens are
skipped. If Enter is pressed the following screens are displayed to permit
refrigerant span calibration.
If the refrigerant monitor is unable to calibrate, the following item shall be
displayed.
Unable to Calibrate
Please Wait
Successful Calibration
Calibration Failed
Starting The Calibration
Please Wait
Unable To Calibrate
XXXX
CVRC-M-1D