Field Startup

AF Proportional Speed Gain

AF Proportional Speed Gain:
Press <+> < -> to Change Setting
Range of values is 1 to 100 in increments of 1. Factory default is 50.
Minimum Capacity Timer Enable
Minimum Capacity Timer:
Press <+> < -> to Change Setting
The choices for Status are: Enable (Factory default), Disable, Unlimited
time.
Note: On Non Adaptive Frequency chillers this Timer times out when the
chiller is at minimum IGV position and the Leaving Water Temp is below
the CWS. On Adaptive Frequency chillers this Timer times out when the
chiller is at minimum IGV position or minimum AF speed (42 Hz) and
LWT < CWS.
X.XX
[Status]
65