Field Startup

ICS Address

ICS Address:
Press <+> <-> to Change Setting
Range of values is 1 to 127 in increments of 1. Factory default is 65.

Power Up Start Delay Time

Help Note: sed primarily for scheduling multiple units or to minimi e
current inrush.
Power Up Start Delay Time:
Press <+> <- > to Change Setting
Range of values is 0 to 600 seconds. Factory Default is 0 seconds.

Design Delta Temperature Setpoint

Design Delta Temp Setpoint:
Press <+> <- > to Change Setting
Range of values is 4 to 30 F (2.2 to 16.7 C) in increments of 1 or 0.1 F or
C depending on the Service Setup Screen XXX or XXX.X. Factory
default is 10 F (5.5 C).
Leaving Water Temperature Cutout Setpoint
Lvg Wtr Temp Cutout Setpoint:
Press <+> <- > to Change Setting
Range of values is -10 to 36° F (-23.3 to 2.2° C) in increments of 1 or
0.1° F or C depending on the Service Setup Screen XXX or XXX.X.
Factory default is 36.0° F (2.2° C).
When this setpoint is within 1.7° F of the Front Panel Chilled Water
Setpoint, the Front Panel Chilled Water Setpoint is increased along with
this setpoint to maintain the differential. A message will be displayed for 2
seconds to indicate that the Front Panel Chilled Water setpoint has been
increased.
Low Refrigerant Temperature Cutout Setpoint
Low Rfgt Temp Cutout Setpt:
Press <+> <- > to Change Setting
Range of values is -35 to 36° F (-37.2 to 2.2° C) in increments of 1 or
0.1° F or C depending on the Service Setup Screen XXX or XXX.X. Fac-
tory default is 32.0° F (0.0° C).
XX
XXX Seconds
XXX.X F/C
XXX.X F/C
XXX.X F/C