Refrigerant Monitor Settings Group

Refrigerant Monitor Settings Group Password Request
This item is displayed if IPC refrigerant monitor is installed.
Pswd Req. to Access Rfqt Mon Settings Group
The Refrigerant Monitor Settings Password is
Enter.
Successfully entering the password sends you to the Refrigerant Monitor
Settings Group Heading Screen.
Refrigerant Monitor Calibration Group Password
Request
This item is displayed if IPC refrigerant monitor is installed.
Pswd Red to Access Rfqt Mon Calibration Group
The Refrigerant Monitor Calibration Passwords are
Enter for field calibration.
Successfully entering password sends you to the Refrigerant Monitor
Calibration Heading Screen.
Service Settings
(Password Protected Refrigerant Monitor Settings Group)
If the refrigerant monitor settings password is entered, the display goes
to the menu defined below. If a key is not pressed every 10 minutes in
this password protected menu, the display returns to the Chiller
Operating Mode display of the Chiller Report, and the password must be
entered again to return to this menu.
Refrigerant Monitor Settings Group Heading
Refrigerant Monitor Group Settings
Press <+> <-> To Change Setting
This header is not suppressed when the headers are suppressed in the
Service Settings menu.
Alarm Level 1
Alarm Level 1:
Press <+> <-> To Change Setting
Range of values are 3 to Alarm Level 2 minus 1 in increments of 1. The
maximum value for R-123 is 30.
Alarm Level 2
Alarm Level 2:
Press <+> <-> To Change Setting
Range of values are Alarm Level 1 plus 1 to Alarm Level 3 minus 1 in
increments of 1.
Please Enter Password
Please Enter Password
XXXX PPM [Rfgt Type]
XXXX PPM [Rfgt Type]
-
-
-
-
-
-
77