Refrigerant Monitor Settings Group
Auxiliary Input
Auxiliary Input:
Press <+> <-> To Change Setting
Possible values of status are: Installed, Not Installed.
Auxiliary Input Alarm
The following items shall be displayed only if the Auxiliary Input is
installed.
Auxiliary Input Alarm:
Press <+> <-> To Change Setting
Possible values of status are: Enable, Disable
Auxiliary Input Alarm Level:
Press <+> <-> To Change Setting
Range of values is 4.0 to 20.0 in increment of 0.1.
Auxiliary Input Alarm Direction:
Press <+> <-> To Change Setting
Possible values of Direction are: Above, Below
Auxiliary Input Audible Alarm:
Press <+> <-> To Change Setting
Possible values of Status are: Disable, Enable
Analog Output Range
Analog Output Range:
Press <+> <-> To Change Setting
Possible values of Range are: 0-100, 0-1000
[Status]
[status]
XX.X mA
[Direction]
[Status]
[Range] PPM