Machine Configuration Group:
Menu item
1
Unit Frequency
2
Unit Type
3
Nominal Unit Tons
4
Refrigerant Type
5
Refrigerant Monitor Type
6
Starter Type
7
Level 2 Contactor Integrity Test
(Startup Contactor Test-Y-D only)
8
Rated Load Amps
9
Motor Heating Constant
10
Current Overload Setting # 1
(See Manual for Setup Procedure)
11
Current Overload Setting # 2
(See Manual for Setup Procedure)
12
Maximum Accel Time Setpt # 1
(See Manual for Recommend Setpt)
13
Maximum Accel Timer Setpt # 2
(255 Minus Timer Setpt #1 above)
14
Heatsink Start Inhibit Temperature Setpoint
15
External Chilled Wtr Setpoint
16
External Current Limit Setpt
17
Acceleration Time Out Action
18
Motor Temp Protection
19
Motor Winding RTD Type
20
High Pressure Cutout setting
21
Line Voltage Sensing Option
22
Unit Line Voltage
23
Hot Gas Bypass Option
24
Condenser Press. Sensor Option
25
Bearing Temp Sensors Option
26
Discharge Temp Sensor Option
27
Ice Building Option
28
External Analog Inputs
29
Tracer Option
30
TCI Option
16
FastPak
"Settings Group" Menu Record
Choices
60 HZ, 50 HZ
CVHE & CVHG, CVHF, CVHB, CVGE, CVAE,
FastPak Water Cooled, FastPak Air Cooled
100 to 1800 Tons
R11, R123, R12, R134a, R22, R113, R114,
R500, R502
None, lPC
Undefined, Adaptive Frequency, Y-Delta,
X-Line, Solid State, Auto Transformer, Primary
Reactor, AFDB, SMCDP, Stand Alone No Str
Module
Disable, Enable
(Not available on any FastPak models)
0 to 2,500
0 to 100 Minutes
00 to 31
224 to 255
6 to 64 Seconds
191 to 249 Seconds
100.0 to 200.0 °F (37.8 to 93.3 °C), in
increments of 0.1 °F/°C
Installed, Not Installed
Installed, Not Installed
Shutdown, Transition
3 Winding Sensors, MTC Switch
100 Ohm/ 0° C, 75 Ohm/ 75 °C
-5 to 500 PSIG
Installed, Not Installed
180 to 6600
Installed, Not Installed
Installed, Not Installed
Installed, Not Installed
Installed, Not Installed
Installed, Not Installed
4-20 ma, 2-10 vdc
Installed, Not Installed
Installed, Not Installed
Default
Design/Actual
60 HZ
CVHE
300 Tons
R123
None
Y-Delta
Disable
500
25 Minutes
00
255
27 Seconds
228 Seconds
100 °F (93.3 °C)
Not Installed
Not Installed
Shutdown
3 Winding Sensors
75 Ohm /75 ° C
15 PSIG for standard unit
25 PSIG for ASME unit
Not Installed
460
Not Installed
Not installed
Not installed
Not installed
Not installed
4-20 ma
Not Installed
Not Installed
CVRC-M-1D