Trane CVRC-M-1D Manual page 87

Table of Contents

Advertisement

CVRC-M-1D
Service Test Group
Hot Gas Bypass Valve Control Status/Manual Open and
Close Commands
If HGBP is installed in the unit the following screen shall be displayed.
HGBP Valve Control Is:
LWT = XX X fc
The possible values of [Status] are "Auto", "Open", or "Close". Factory
Default is "Auto".
The possible values of Y are: "Current Limit", "Condenser Limit", "Evap
Limit", and "(+) (-) and (Enter)".
The latter is displayed when there are no limits operating.
Hot Gas Bypass Valve Manual Opening/Closing Duty
Cycle
The following screen will be displayed only when the "Inlet Guide Vane
Output" is set to "Pulsed".
ManualOpening/ClosingDutyCycle:
Press <+> <-> To Change Setting
Range of Values is 0 to 50% in increments of 1%. Factory Default is 30%.
Manual Fan Control FastPak Air Cooled Only
The following screen will be displayed only for FastPak Air Cooled
Products.
FastPak AirCooled Only
Press <+> <-> To Change Setting
The possible values of [status] are "Auto" or "Enable".
Compressor Speed Command
The following menu will be displayed only if the Starter Type is Adaptive
Frequency and Adaptive Speed Control Algorithm is Enabled.
CVHE/F/G Only Compressor Speed Command:
Compressor Speed Command:
Fan Control:
[status]
XXXX.X RPM
Status
[Y]
XX%
XX.X Hz
87