Parameterizing The 3Rw5 Hmi High Feature - Siemens SIRIUS 3RW55 Equipment Manual

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW55:
Table of Contents

Advertisement

Result
As many as 4 start functions have been assigned to the start key. These functions can be selected
and executed after actuating the start key.
6.10

Parameterizing the 3RW5 HMI High Feature

Setting options
• 3RW5 HMI High Feature
Menu: "Parameters > HMI"
Access protection to the 3RW5 HMI High Feature is not active or has been reset.
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Parameters" > Window "Work area" > "HMI"
• With a fieldbus via a 3RW5 communication module:
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional (only via a 3RW5 PROFINET
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– User program
You can find additional information on the parameters that can be set via the fieldbus in the
manual of the respective 3RW5 communication module.
Parameter
Parameters
Local interface activated
(via 3RW5 HMI High Feature only)
Local interface deactivated
(via 3RW5 HMI High Feature only)
Timer lighting dark
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
or PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
Description
The parameter is only visible if the local interface is enabled (factory setting).
Disables the local interface of the 3RW5 HMI High Feature.
Before you can connect a PC with SIRIUS Soft Starter ES (TIA Portal) and the 3RW55 or
3RW55 Failsafe soft starter via the local interface, the local interface must be enabled.
You can prevent unauthorized access via SIRIUS Soft Starter ES (TIA Portal) by disabling
the local interface.
The parameter is only visible if the local interface is disabled.
Enables the local interface of the 3RW5 HMI High Feature.
If no keys on the 3RW5 HMI High Feature are pressed, the display will shut down after a
specified time period has elapsed. The setting "0 min" deactivates shutdown of the
display.
Factory setting: 5 min
Setting range: 0 ... 60 min
In steps of: 1 min
6.10 Parameterizing the 3RW5 HMI High Feature
Parameter assignment
121