Example circuits
A.3 Special applications
Basic configuration
Safe shutdown up to SILCL 3 according to IEC 62061 / PL e according to EN ISO 13849‑1 requires
the use of 2 redundant contactors and monitoring of the auxiliary contacts of both contactors.
Two-channel monitoring of the EMERGENCY STOP is also required here.
①
②
③
④
⑤
340
EMERGENCY STOP
3RT20 contactors
3RW55 soft starter
Motor
3SK1 safety relay
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006