7.3

First commissioning of the High Feature 3RW5 HMI

Requirements
• Power supply (control supply voltage) is connected for the first time or the factory settings
have been restored on the 3RW5 HMI High Feature.
• Design and operator controls of the High Feature 3RW5 HMI (Page 98)
Procedure
1. Select the desired language and confirm with the OK key.
2. Set the date and time and confirm the menu after setting the parameters with the right-hand
navigation key.
You can use the left-hand navigation key to switch back to language selection.
3. Save the settings by confirming one of the three following menu entries with the OK key or
exit the menu without saving the settings ("Don't save startup parameters and exit").
– "Save startup parameters and start application wizard"
– "Save startup parameters and start automatic parameterization"
– "Save startup parameters and exit"
Result
The 3RW5 HMI High Feature is ready to use. You will find an overview of the functions in
chapter 3RW5 HMI High Feature (Page 28). Note the menu structure in chapter Menu of the
3RW5 HMI High Feature (Page 99).
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
The 3RW5 HMI High Feature switches to the application wizard (Page 92) menu.
The 3RW5 HMI High Feature switches to the automatic parameterization (Page 132)
menu.
The 3RW5 HMI High Feature switches to the operation display.
7.3 First commissioning of the High Feature 3RW5 HMI
Commissioning
127