5.4.12
Diagnostics, Wire break
Definition
Enabling the wire break diagnostics. A wire break diagnostic message occurs if it is detected that
the current flow is too low.
Monitoring is effective from an output current of ≥ 240 µA.
If the output current drops below 240 µA when the "Wire break" diagnostics message is pending,
the diagnostic message cannot be canceled until the output current is set above 240 µA again
and the error has been eliminated.
5.4.13
Diagnostics encoder supply
Definition
The sensor supply of the analog input is monitored for overload and short-circuit to M. To
prevent a thermal overload situation, the sensor supply is switched off, if required, with cyclical
repowering attempts.
5.4.14
Hardware interrupt 1 / 2
Definition
A hardware interrupt is enabled if the high limit 1 / 2 is exceeded or low limit 1 / 2 is violated.
5.4.15
High limit 1/2
Definition
Specify a high threshold which triggers a hardware interrupt when violated.
5.4.16
Low limit 1 / 2
Definition
Specify a low threshold which triggers a hardware interrupt when violated.