Functions
8.13 Outputs
8.13.2

Analog output

Operating principle
The set measured value is displayed via the analog output using an external evaluation unit.
Depending on the respective connecting terminal being used, the signal can be displayed either
as current or voltage.
• Terminals: AQ- / AQ I+
Measuring range of current output: 4 - 20 mA
• Terminals: AQ- / AQ U+
Measuring range of voltage output: 0 - 10 V
Requirements
Evaluation unit is connected properly (Page 304).
Setting options
• 3RW5 HMI High Feature
Menu: "Parameters > Soft Starter > Outputs > Analog output"
Access protection to the 3RW5 HMI High Feature is not active or has been reset.
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Parameters" > Window "Work area" > "Soft Starter > Outputs > Soft Starter > Analog output"
• With a fieldbus via a 3RW5 communication module:
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional (only via a 3RW5 PROFINET
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– User program
You can find additional information on the parameters that can be set via the fieldbus in the
manual of the respective 3RW5 communication module.
202
or PROFIBUS communication module)
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006