Test With Small Load - Siemens SIRIUS 3RW55 Equipment Manual

Soft starters and solid-state switching devices
Hide thumbs Also See for SIRIUS 3RW55:
Table of Contents

Advertisement

Functions
8.19 Test mode
Setting options
Automatic starting in test operation (test with a small load and simulation)
Can cause death or serious injury.
The 3RW55 and 3RW55 Failsafe soft starters immediately continue to operate with the values
set by the control once test operation has been activated. Outputs are activated when the ON
condition is met.
Take appropriate measures to prevent unintentional starting and to ensure a defined start of
the system.
• 3RW5 HMI High Feature (from firmware version V2.0)
Access protection to 3RW5 HMI High Feature is not active or has been reset.
Menu: "Control > Test mode"
Note
Activating test mode
If you activate or deactivate "Test with small load" or the "Simulation" on the 3RW5 HMI High
Feature, you will automatically also switch to Test mode or Normal operation. For activation
and deactivation on the 3RW5 HMI High Feature, the 3RW5 HMI High Feature must have
master control.
• With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the 3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Commissioning" > Window "Work area" > "Soft Starter > Functions > Test mode"
• With a fieldbus via a 3RW5 communication module (only via a 3RW5 PROFINET or PROFIBUS
communication module):
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– User program
8.19.1

Test with small load

Operating principle
The test mode function "Test with small load" is helpful during commissioning and when
troubleshooting, as the correct function of the application can be tested before installation in a
control cabinet or before the use of a motor provided for the application. The "Test with small
load" provides a way of checking the wiring of the control and main circuit with the aid of a small
motor (test motor).
222
WARNING
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006