3.3 Operating principle
Canceling the switch-on command (t
The power semiconductors also ensure that the motor coasts down smoothly to a stop. As long
as the stopping time is active (t
the motor to actually coast down to a standstill (t
t
1
t
2
t
3
t
4
Functions of the 3RW55 and 3RW55 Failsafe soft starters
Note the information in chapter Firmware update (Page 22).
• Parameterizable soft starting for a smooth drive start-up
• Parameterizable soft stopping for a smooth drive stop
• Parameterizable current limiting for avoiding current peaks
• Integrated electronic motor overload protection with adjustable trip class (OFF,
CLASS 10A, 10E, 20E, 30E)
• Integrated intrinsic device protection protects the 3RW55 and 3RW55 Failsafe soft starters
from overload
• Extended complete motor protection by means of thermistor motor protection for
connection of a temperature sensor
• Extended operating and diagnostic functions provided by the High Feature 3RW5 HMI
• Analog output for displaying a set measured value using an external evaluation unit
• Automatic parameterization simplifies system commissioning
26
Speed
Voltage
Motor start-up with set starting voltage U
Rated operating speed n
reached
e
End of the set ramp-up time
(t
-t
)
3
1
Switch-on command is canceled, motor is
switched off
) activates the stopping mode and the motor is shut down.
4
to t
), power is still supplied to the motor. It may take longer for
4
5
).
6
t
End of the set stopping time
5
(t
t
Motor at standstill
6
U
Set starting voltage
S
S
U
Rated operational voltage
e
n
Rated operating speed of the motor
e
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006
-t
)
5
4
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters