IO-Link Configuration Page

You can use the Configuration | IO-Link Settings page to configure IO-Link port settings. When the
IO-Link device is attached to a port, it begins operating without requiring any configuration. The IOLM
and attached IO-Link device automatically negotiate the Minimum Cycle Time. If required by an
application, you can set a specific Minimum Cycle Time.
This page provides special features such as Data Storage, Device Validation, and Data Validation.
Although you can make configuration changes using the web page, PROFINET IO configuration
parameters overwrite the values on the IO-Link Settings page. See Section 3: Configuring the IOLM with
PAC Machine Edition for detailed configuration procedures.
Figure 40: IO-Link Configuration Page
6.2.1

Editing IO-Link Port Settings

You can use this procedure to configure IO-Link settings for each IO-Link port.
If an IO-Link device is attached to the port, no configuration is required for operation. If a digital input
or output device is attached, it is necessary to change the Port Mode.
1. If necessary, open the IO-Link Master web interface with your web browser using the IP
2. Click Configuration | IO-Link Settings.
3. Click the EDIT button for the port or ports that you want to configure.
IO-Link Master Port Configuration
address.