3.4

IP Address Assignment

RSTi-OM IOLM gateways support three methods for IP address assignment according to GSDML
Specification.
3.4.1

Assigning an IP Address via IO Controller (DCP)

A PROFINET IO controller can assign an IP address to the IOLM gateway via DCP. The IO controller and
the Emerson IOLM gateway have to be on the same subnet. The IOLM default IP address is:
192.168.11.202 and the subnet mask is 255.255.255.0.
To assign IP address/device name from the DCP tool, navigate to Utilities menu item in PAC Machine
Edition and select PROFINET DCP
Figure 11: PROFINET DCP Utility
The PROFINET DCP dialogue will pop up. Select the appropriate connection to which the PROFINET
controller and IO device are connected. Click on Refresh Device List to list all PROFINET controllers and
IO devices connected.
Figure 12: PROFINET Connection
Any unconfigured device will be indicated by the blank Device Name field. Click on the device to
which the device name or IP address is to be assigned.
Configuring
DCP - The IOLM supports IP address assignment via Discovery and basic Configuration
Protocol (DCP). See 3.4.1 Assigning an IP Address via IO Controller (DCP) for procedures.
DHCP - The IOLM supports the Dynamic Host Configuration Protocol for IP address
assignment. See 3.4.2, Assigning an IP Address via DHCP for procedures.
LOCAL - The IOLM supports a device-specific method for IP address assignment. See Section
Assign IP Address Statically Using the Web Page.