4.1.2

Application Subassemblies

Application sub-assemblies are the components of the Application Base image. Application sub-
assemblies have a 4-tuple version number (for example, 1.3.18.3). The first two values in a
subassembly version correspond to the version of the application base assembly for which it was built
and tested.
For example, a subassembly with version 1.3.18.3 was tested with application base version 1.3.18.
When using the Software page, an application subassembly can install only if its version number
matches that of the installed application base assembly. A subassembly with a version of 1.20.2.4 only
installs if the application base version is 1.20.2. It will not install on a device with application base
version 1.21.5.
application-manager
configuration-manager
discovery-protocol
event-log
iolink-driver
libiolinkutils
modbus
opcua-server
profinetio
web-help
web-user-interface
4.2

Using the Web Interface to Update Software

The upper portion of the Advanced | Software page is used to update the IOLM images. The lower
portion of this page is used for updating application sub-assemblies that are integrated into the
Application Base.
Typically, the latest application sub-assemblies are available in the Application Base image. There may
times when a feature enhancement or bug fix is available in an application subassembly and not yet
available in the Application Base image.
4.2.1

Updating Images

Use this procedure to upload images using the SOFTWARE page.
1. Download the latest image from the
Note: Make sure that you download the appropriate software for your model. For example, the FPGA
images are unique for different hardware models and protocols.
2. Open your browser and enter the IP address of the IOLM.
3. Click Advanced | SOFTWARE.
4. Click the UPDATE button next to the image you want to update.
5. Click the Browse button, navigate to the file location, highlight the image, and click Open.
Updating the IOLM Firmware and Application Files
IOLM Application Sub-assemblies
The Application Manager version is loaded on the IOLM.
The Configuration Manager version is loaded on the IOLM.
The Discovery Protocol version is loaded on the IOLM.
The Event log version is loaded on the IOLM.
The IO-Link driver version is loaded on the IOLM.
IOLM Application Sub-assemblies (Continued)
The IO-Link utility library version is loaded on the IOLM.
If applicable, the Modbus/TCP interface version is loaded on the IOLM.
If applicable, the opc ua-server interface version is loaded on the IOLM.
The PROFINET IO version is loaded on the IOLM.
The web interface help version is loaded on the IOLM.