Standard Default Setting - Toshiba TOSVERT VF-S11 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

5.6

Standard default setting

Title
5
This function will be displayed as 0 during reading on the right. This previous setting is displayed.
Example:
Programmed value
Default setting (
Setting
(Refer to 4.2.6)
✩ When 3 is programmed, <
Trip clear (
Setting
✩ The parameter does not change.
Cumulative operation time clear (
Setting
Cumulative operation time clear (
Setting typ to
us.
: Default setting
Function
Allows setting of all parameters to the standard default setting, etc. at one time.
Note that fm, fmsl, f109, f470 ∼ f473, f669 and f880 will not be reset to their
factory default settings.
Function
Default setting
cannot be set during the inverter operating. Always stop the inverter first and then program.
=
)
to
will return all parameters to the standard values that were programmed at the factory.
and displayed the original indication 0.0. Trip history data will be cleared at this time.
=
)
to
initializes the past four sets of recorded error history data.
to
resets the cumulative operation time to the initial value (zero).
clears the trips when an
Adjustment range
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Standard default setting
(Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user-defined parameters
8: Call user-defined parameters
9: Cumulative fan operation time
record clear
will be displayed for a short time after setting and will then be erased
=
)
=
)
format error occurs. But if the
E-14
E6581158
Default setting
0
displayed, call