Setting of motor electronic thermal protection level 1
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller
than the rated current of the inverter, adjust the electronic thermal protection level 1 so that it fits the motor's
rated current.
[Example of setting: When the VFAS1-2007PL is running with a 0.4kW motor having 2A rated current]
Key operated
5
MODE
ENT
ENT
[Using a VF motor (motor for use with inverter)]
Setting of electronic thermal protection characteristics selection
Default setting
A VF motor (a motor for use with an inverter) can be used in lower frequency ranges than the general-purpose motor,
but if that frequency is extremely low, the effects of cooling on the motor will deteriorate.
In such a case, set the OL reduction start frequency parameter according to the characteristics of the motor.
(Refer to the figure below.)
As a guide, it is advisable to set this parameter around the default value (VF motor 6Hz).
[Parameter setting]
Title
Note: is enabled when =~.
Output current reduction factor [%]/[A]
×1.0
×0.6
0
Note:The motor overload starting level is fixed at 30Hz. If necessary, set to ~.
(See the following section.)
LED display
Displays the operation frequency. (Perform during operation stopped.)
(When standard monitor display selection = [Operation
frequency])
The first basic parameter "History function ()" is displayed.
Press either the
Press the ENTER key to display the parameter setting (Default setting:
%).
Press the
(= motor rated current/inverter output rated current x 100
Press the ENTER key to save the changed parameter. and the
⇔
parameter are displayed alternately.
Overload protection
(protect)
(protect)
× (not protect)
× (not protect)
Function
OL reduction starting frequency
30Hz
Operation
key or the
key to change the parameter to .
key to change the parameter to
= 2.0/5.0 × 100)
Overload stall
× (not stall)
(stall)
× (not stall)
(stall)
Adjustment range
~ [Hz]
E-22
E6581301
Output frequency [Hz]
Default setting