Selecting Forward And Reverse Runs (Operation Panel Only - Toshiba TOSVERT VF-AS1 Instruction Manual

The new generation high-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

5.13

Selecting forward and reverse runs (operation panel only)


• Function
Program the direction of rotation of the motor when the running and stopping are made using the RUN key and
STOP key on the operation panel.
Valid when  (command mode selection) = (operation panel input).
Parameter setting
Title

Check the direction of rotation on the status monitor.
: Forward run
⇒ For monitoring, refer to Section 8.1.
When the F and R terminals are used for switching between forward run and stop from the terminal board, the 
5
forward/reverse run selection parameter is rendered invalid.
If F and CC, as well as R and CC are connected at the same time: Stop (Default setting)
Use the parameter  to select between reverse run and stop in this case.
⇒ For more details, refer to Section 6.2.1.
This function is valid only when  is set at  (Operation panel input enabled).
When =,  press the
and reverse run.
: Forward/reverse run selection
Function
Forward/reverse run selection
: Reverse run
Short across the F-CC terminals: forward run
Short across the R-CC terminals: reverse run
and
ENT
Adjustment range
: Forward run
: Reverse run
: Forward run (F/R switching possible)
: Reverse run (F/R switching possible)
keys on the operation panel at a time to switch between forward run
E-20
E6581301
Default setting