13. Before making a service call
13.1
Trip causes/warnings and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the table,
contact your supplier.
[Trip information]
Error
Description
code
Overcurrent
during
acceleration
Overcurrent
during
deceleration
Overcurrent
during fixed
speed
[Note] , ,
originate from
causes other than those
mentioned above.
Overcurrent
(loaded side
overcurrent at
start time)
U-phase arm
short-circuit
V-phase arm
short-circuit
W-phase arm
short-circuit
Input phase
failure
*
Output phase
failure
Overvoltage
during
acceleration
Overvoltage
during
deceleration
*Presence or absence of parameter trip can be selected.
(Continued overleaf)
Possible causes
•The acceleration time is too short.
•The V/f setting is improper.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•A special motor (e.g. motor with a
small impedance) is used.
•Manual torque boost value () is large.
•The deceleration time is too
short. (in deceleration)
•The load fluctuates abruptly.
•The load is in an abnormal
condition.
•A main circuit elements is defective.
•Overheat protection is activated.
•The insulation of the output main
circuit or motor is defective.
•The motor has too small
impedance.
•A main circuit elements is defective
(U-phase).
•A main circuit elements is defective
(V-phase).
•A main circuit elements is defective
(W-phase).
•A phase failure occurred in the
input line of the main circuit.
•A phase failure occurred in the
output line of the main circuit.
•The input voltage fluctuates abnormally.
(1)The power supply has a capacity
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•The deceleration time is too
short (regenerative energy is too
large).
•The dynamic braking resistor has a
considerably large resistance.
• (Dynamic braking resistor) is OFF.
Overvoltage limit operation
is OFF.
•The input voltage fluctuates abnormally.
(1)The power supply has a capacity
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
M-1
- Trip information and remedies
Remedies
•Increase the acceleration time .
•Check the V/f parameter setting.
•Use (Auto-restart) and (Regenerative
power ride-though control).
•Increase the carrier frequency .
•Decrease setting value.
•Increase the deceleration time .
•Reduce the load fluctuation.
•Check the load (operated machine).
•Make a service call.
•Check operation of cooling fan.
•Check cooling fan control mode parameter
.
•Check the cables and wires for defective
insulation.
•Selection of short circuit detection at starting
parameter .
•Make a service call.
•Make a service call.
•Make a service call.
•Check the main circuit input line for phase failure.
•Check the main circuit output line, motor, etc. for
phase failure.
•Select output phase failure detection parameter
.
•Insert a suitable input reactor.
•Use (Auto-restart) and (Regenerative
power ride-though control).
•Increase the deceleration time .
•Install a dynamic braking resistor.
•Decrease dynamic braking resistance. (Also reset
the .)
•Set dynamic braking mode parameter
properly.
•Set overvoltage limit operation properly.
•Insert a suitable input reactor.
E6581301