6.33.13 Abnormal speed detection
: Abnormal speed detection time
: Overspeed detection frequency upper band
: Overspeed detection frequency lower band
• Function
These parameters allow you to set the inverter so that, when it is in sensor speed control mode (=,
), it always monitors the rotational speed of the motor, even when the motor is at rest, and if the speed
remains out of the specified limits for the specified length of time, it outputs an error signal.
Title
Output frequency [Hz]
6
6.33.14 Overvoltage limit operation
: Overvoltage limit operation level
⇒ For more details, refer to Section 6.14.2.
6.33.15 Undervoltage trip
: Undervoltage detection level
: Undervoltage trip selection
: Undervoltage (trip alarm) detection time
• Function
This parameter is used for selecting the control mode when an undervoltage is detected. (Invalid, while the
inverter stops.) When selecting "tripping enabled," you can also specify the time elapsed before the inverter
trips.
=: (Deselect) ・・・・・・・・・ Inverter stops,but does not trip. (FL is not active.)
=: (Select) ・・・・・・・・・・・ The inverter trips if an undervoltage passes for the time set with or over.
Title
Function
Abnormal speed detection time
Overspeed detection frequency upper
band
Overspeed detection frequency lower
band
0
(FL is activated.)
Function
Undervoltage detection level
Undervoltage trip selection
Undervoltage (trip alarm) detection time
Adjustment range
~ sec.
: Disabled, ~ H z
: Disabled, ~ H z
Output frequency
trip
Adjustment range
~%, %: (auto mode)
: Deselect, : Select
~ sec.
F-60
E6581301
Default setting
Time [s]
Default setting