4) Minimum resistance of connectable braking resistors
The minimum allowable resistance values of the externally connectable braking resistors are listed in the table
below.
Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance
values.
(For 200kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.)
Inverter
Related output capacity
Resistance of
(kW)
standard option
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
220
280
[200V Class]
Minimum allowable
resistance
200Ω
50Ω
200Ω
50Ω
75Ω
35Ω
75Ω
25Ω
40Ω
16Ω
20Ω
11Ω
15Ω
8Ω
10Ω
5Ω
7.5Ω
5Ω
7.5Ω
5Ω
3.3Ω
3.3Ω
3.3Ω
3.3Ω
2Ω
1.7Ω
2Ω
1.7Ω
2Ω
1.7Ω
1.7Ω
1.3Ω
E-41
[400V Class]
Resistance of
Minimum allowable
standard option
resistance
200Ω
60Ω
200Ω
60Ω
200Ω
60Ω
160Ω
40Ω
80Ω
30Ω
60Ω
30Ω
40Ω
20Ω
30Ω
20Ω
30Ω
15Ω
15Ω
13.3Ω
13.3Ω
13.3Ω
8Ω
6.7Ω
8Ω
8Ω
8Ω
3.3Ω
3.7Ω
3.3Ω
3.7Ω
2.5Ω
3.7Ω
2.5Ω
3.7Ω
1.3Ω
1.9Ω
1.9Ω
1.4Ω
E6581301
5
5Ω
5Ω
1Ω
1Ω
1Ω