4 IQ-SENSE
Note
Unused channels of the module must be deactivated otherwise the wire break
diagnosis will be reported.
Measurement type parameter: Deactivated
All the diagnoses are suppressed.
Sensitivity/distance values and circuit states are set to "0".
The sensor is switched off.
14.1.1
Group diagnosis parameter
If you enable group diagnosis, a queued diagnostic message is entered. See
Section 6.6.8 Channel-specific diagnosis.
14.1.2
Synchronization group parameter
Features
• Sensors of different modules of the 4 IQ-SENSE can affect one another with
scattered light, for example.
• To prevent this interference between adjacent sensors on different modules,
you can assign each module a separate synchronization group with this
parameter. Modules with different synchronization groups do not affect each
other.
• It is not possible for sensors on the same module to affect one another.
14-4
ET 200S Distributed I/O System
EWA-4NEB780602402-09