Siemens SIMATIC ET 200S Manual page 183

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

4 IQ-SENSE
Table 6-24 4 IQ-SENSE
Error type
1
00001: Short circuit
D
6
00110: Open circuit
D
8
01000: Lower limit violation
D
9
01001: Error
D
16
10000: Parameter
D
assignment error
26
11010: External fault
D
27
11011: Unclear error
D
ET 200S Distributed I/O System
EWA-4NEB780602402-09
Meaning
Short circuit of the lines
between the electronic module
and sensor
Line to the actuator interrupted.
No sensor connected.
Sensor does not respond.
Maintenance requirement
(signal quality < 130 %, excess
gain), sensor-dependent
Communication error between
the electronic module and
sensor
Parameter assignment error.
Inserted module does not
match the one configured.
Teach-in error (a new value
could not be
determined/obtained)
Inserted sensor does not match
configured sensor.
Excess gain lower limit violated
(signal quality < 110 %) or
sensor error, sensor-dependent
Teach-in process running.
Alignment tool is active.
Commissioning and Diagnostics
What to do
Check the wiring to the sensor.
Correct the process wiring.
Correct the process wiring.
Connect the sensor.
Replace the fuse.
Adjust the reflex sensor.
Clean the optical system.
Replace the electronic module
or the sensor.
Check the wiring.
Adjust the parameter
assignment.
Correct the configuration
(compare actual and desired
configuration).
Repeat teach-in.
Correct the configuration, or
insert a different sensor type.
Adjust the reflex sensor.
Clean the optical system.
Replace the sensor.
Terminate the teach-in process.
Terminate the alignment tool.
6-49

Advertisement

Table of Contents
loading

Table of Contents