Siemens SIMATIC ET 200S Manual page 201

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Note
All of the supply and load voltages of the ET 200S must not exceed 24 VDC. This
voltage limit must be enforced.
Mechanical environmental conditions
The mechanical environmental conditions are shown in the following table in the
form of sinusoidal oscillations.
ET 200S modules
Everything except motor star-
ters
Testing mechanical environmental conditions
The following table provides information on the type and extent of tests of
mechanical environmental conditions.
Test for ...
Test Standard
Oscillations
Oscillation test in
accordance with
IEC 60068-2-6
Shock
Shock test to
IEC 60068-2-27
Repetitive
Shock test to
shock
IEC 60068-29
ET 200S Distributed I/O System
EWA-4NEB780602402-09
Frequency
Permanent
range
10 v f v 58 Hz
0.15 mm amplitude
58 v f v 150 Hz
2 g constant acceleration 5 g constant acceleration
Terminal modules and electronic modules
Oscillation type: frequency sweeps with a rate of change of 1 octave
per minute.
10 Hz v f v 58 Hz, constant amplitude 0.35 mm
58 Hz v f v 150 Hz, constant acceleration 5 g
Oscillation time: 20 frequency sweeps per axis on all of the three per-
pendicular axes
Type of shock: half sine
Force of shock: 15 g peak value, 11 ms duration
Direction of shock: 3 shocks per +/– direction in all of the three perpen-
dicular axes
Type of shock: half sine
Force of shock: 25 g peak value, 6 ms duration
Direction of shock: 1000 shocks per +/– direction in all of the three per-
pendicular axes
General Technical Specifications
Occasional
0.35 mm amplitude
7-9

Advertisement

Table of Contents
loading