1Pos Inc/Digital, 1Pos Ssi/Digital, 1Pos Inc/Analog - Siemens SIMATIC ET 200S Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

2PULSE
Table 6-21 2PULSE
Error type
1
00001: Short circuit
D
9
01001: Error
D
16
10000: Parameter
D
assignment error
1POS INC/Digital, 1POS SSI/Digital, 1POS INC/Analog, 1POS SSI/Analog
Table 6-22 1POS INC/Digital, 1POS SSI/Digital, 1POS INC/Analog, 1POS SSI/Analog
Error type
1
00001: Short circuit
D
16
10000: Parameter
D
assignment error
17
10001: Load voltage 2L+
D
missing
26
11010: External fault
D
ET 200S Distributed I/O System
EWA-4NEB780602402-09
Meaning
Short circuit of the sensor
supply or the actuator.
Internal module error occurred.
Parameters have not been
assigned to the module.
Meaning
Short circuit of the sensor
supply.
Parameters have not been
assigned to the module.
Only applies to the 1POS
INC/Digital and 1POS
SSI/Digital:
No supply voltage, or
inadequate supply voltage
Wire break/short circuit of the
sensor signals:
Wire break in the sensor cable
or sensor cable is not
connected.
Sensor is defective or there are
faults.
Sensor type, transmission rate,
and monoflop time do not
correspond to the sensor
connected; programmable
sensors do not correspond to
the settings on the module.
Commissioning and Diagnostics
What to do
Check the wiring to the
momentary-contact switches
and the actuators. Correct the
process wiring.
Replace the module.
Adjust the parameter
assignment.
What to do
Check the wiring to the sensor.
Correct the process wiring.
Adjust the parameter
assignment.
Correct the process wiring.
Check the supply voltage.
Correct the process wiring.
Correct the parameter
assignment.
Replace the sensor.
6-47