Analog value generation
Measuring principle
Integration and cycle time/
resolution per channel:
Integration time
parameterizable
Interference frequency
suppression in Hz
Integration time in
milliseconds
Conversion time in ms
Cycle time in ms
Resolution (including
overrange)
Suppression of interference, limits of error
Interference voltage sup-
pression for f = n x (f1
$ 1%), (f1 = interference
frequency)
Common-mode
interference (U
)
pp
Series-mode
interference
(peak interference
value < rated value of
input range)
Crosstalk between the
inputs
Operational limit
(entire temperature range
with reference to input
range)
Basic error limit (operational
limit at 25 _C with reference
to input range)
Temperature error (with re-
ference to the input range)
Linearity error (with refe-
rence to the input range)
Repeatability
(in steady state at 25 _C
with reference to input
range)
ET 200S Distributed I/O System
EWA-4NEB780602402-09
Integrative
Yes
60
50
16.7
20
55
65
Number of active
channels per
module

conversion time
10 V/13 bits +
$
sign
5 V/13 bits + sign
$
1 to 5 V/13 bits
Min. 90 dB
Min. 70 dB
Min. –50 dB
" 0.6 %
"0.4%
"0.01%/K
"0.01%
"0.05 %
Analog Electronic Modules
Data for selecting a sensor
Input range (rated
value)/input resistance
Voltage
Permitted input voltage
(destruction limit)
Smoothing of the measured
values
Step
None
Weak
Medium
Strong
"5 V/min. 100 kW
1 to 5 V/min. 100 kW
"10 V/min. 100 kW
35 V continuous,
75 V for max. 1 ms
(pulse duty factor
1:20)
Yes, parameteriza-
ble in 4 steps by
means of digital filte-
ring
Time constant
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
13-47