Siemens SIMATIC ET 200S Manual page 192

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Commissioning and Diagnostics
6.6.10
Diagnostics in the case of invalid ET 200S configuration states
Invalid configuration states
The following invalid configuration states of the ET 200S lead to station failure of
the ET 200S or prevent entry into data interchange. These responses occur
irrespective of whether the IM parameters "Operation at Preset <> Actual
Configuration", "Replacement of Modules during Operation", and "Startup when
Expected <> Actual Configuration" have been enabled.
• Two missing modules
• Terminating module missing
• Number of modules exceeds the maximum configuration
• Module missing in slot 1 (in the case of the IM151-1 STANDARD,
6ES7151-1AA00-0AB0)
• Faulty backplane bus (for example, terminal module is defective)
Note
As of IM151-1 BASIC/IM151-1 STANDARD (6ES7151-1AA01-0AB0), IM151-1 FO
STANDARD, and IM151-1 HIGH FEATURE: If one module is missing (gap) and
the ET 200S is switched on, the station will not start up (see diagnosis below).
Diagnostics
The following diagnosis indicates all the invalid configuration states:
Interface module
IM151-1 HIGH FEATURE
IM151-1 BASIC
IM151-1 STANDARD
IM151-1 FO STANDARD
6-58
Module diagnosis
All 63 bits set
All 12 bits set
All 63 bits set
Module status
01
: "Module error; invalid user data" for all
B
63 modules
01
: "Module error; invalid user data" for
B
all modules (slots) until the cause of the
(
)
error is found
i f
d
11
: "No module; invalid user data" once
B
the cause of the error is found
ET 200S Distributed I/O System
EWA-4NEB780602402-09

Advertisement

Table of Contents
loading

Table of Contents