Siemens SIMATIC ET 200S Manual page 484

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Analog Electronic Modules
Analog value generation
Resolution (including over-
range)
Cycle time
Settling time
For resistive load
For capacitive load
For inductive load
Substitute value paramete-
rizable
Suppression of interference, limits of error
Crosstalk between the out-
puts
Operational limit (in the en-
tire temperature range, with
reference to the output
range)
Basic error limit (operational
limit at 25 _C with reference
to output range)
Temperature error (with re-
ference to the output range)
Linearity error (with refe-
rence to the output range)
13-100
10 V/13 bits + sign
$
1 to 5 V/12 bits
Max. 1.5 ms
0.1 ms
0.5 ms
0.5 ms
Yes
min. –40dB
"0.4%
"0.2%
"0.01%/K
"0.02%
Repeatability
(in steady state at 25 _C
with reference to output
range)
Output ripple (with refe-
rence to output range,
bandwidth 0 to 50 kHz)
Data for selecting an actuator
Output range (rated value)
Load resistance
For capacitive load
Short-circuit protection
Short-circuit current
Destruction limit against
voltages/currents applied
from outside
Voltage at the outputs to
M
ANA
Current
Connection of actuators
Two-conductor
connection
Four-conductor
connection
ET 200S Distributed I/O System
"0.05%
"0.02%
"10 V
1 to 5 V
Min. 1.0 kW
Max. 1 mF
Yes
Approx. 25 mA
Max. 15 V
continuous; 75 V for
max. 1 s (pulse duty
factor 1:20)
Max. DC 50 mA
Possible, without
compensation of the
line resistances
Yes
EWA-4NEB780602402-09