Power Modules
Note
The PM-E 24–48 VDC, 24–230 VAC power module (6ES7138-4CB10-0AB0) is not
a direct replacement for the device with the order number 6ES7138-4CB00-0AB0
for AC applications because you have to select either AC or DC supply voltage. In
the case of DC applications, the new module is a direct replacement because the
default setting of the new parameter is "DC". If you want to replace the device
6ES7138-4CB00-0AB0 in AC applications, you have to create a new hardware
configuration and set the value "AC" for the load voltage type parameter.
If the hardware configuration is not changed for AC applications, the SF status
LED remains on all the time. If the "No load voltage" diagnostic interrupt is
enabled, several interrupts are activated in each AC cycle. The electronic modules
that are connected to the potential group of this PM-E continue to function
normally, however.
Terminal assignment
The following table indicates the terminal assignment of the PM-E 24–48 VDC,
24–230 VAC power module for the different terminal modules:
View
AUX1
A
A
8
4
24–48 VDC/ L1
2
M/ N
3
A
AUX1
4
AUX1
A
A
8
4
24–48 VDC/ L1
2
M/ N
3
A
AUX1
4
11-12
TM-P15S23-A1 and PM-E 24–48 VDC, 24–230 VAC
24–48 VDC/ L1
6
M/ N
7
A
AUX1
8
TM-P15S23-A0 and PM-E 24–48 VDC, 24–230 VAC
24–48 VDC/ L1
6
M/ N
7
A
AUX1
8
Terminal assignment
Y
AC
24 VDC
Y
AC
24 VDC
Remarks
24–48 VDC/ L1: Rated
load voltage
M/ N: Ground/neutral
conductor
AUX1: Ground terminal
or usable as any
voltage bus up to the
level of the load
voltage.
24–48 VDC/ L1: Rated
load voltage
M/ N: Ground/neutral
conductor
AUX1: Ground terminal
or usable as any
voltage bus up to the
level of the load
voltage.
AUX1 is used as PE.