Siemens SIMATIC ET 200S Manual page 393

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Measuring ranges for resistance thermometer Pt x00 Standard
Table 13-8 SIMATIC S7 format: Measuring ranges Pt 100, 200, 500, 1000 Standard in °C and °F
Pt x00
Units
Standard
in 5C
in 5C
Dec.
(1 digit =
0.15C)
> 1000.0
32767
7FFF
1000.0
10000
2710
:
:
:
850.1
8501
2135
850.0
8500
2134
:
:
:
–200.0
–2000
F830
–200.1
–2001
F82F
:
:
:
–243.0
–2430
F682
< – 243.0
–32768
8000
Measuring ranges for resistance thermometer Pt x00 Climatic
Table 13-9 SIMATIC S7 format: Measuring ranges Pt 100, 200, 500, 1000 Climatic% in °C and °F
Pt x00
Units
Climatic
in 5C
in 5C
Dec.
(1 digit =
0.015C)
> 155.00
32767
7FFF
155.00
15500
3C8C
:
:
:
130.01
13001
32C9
130.00
13000
32C8
:
:
:
–120.00
–12000
D120
–120.01
–12001
D11F
:
:
:
–145.00
–14500
C75C
< – 145.00
–32768
8000
ET 200S Distributed I/O System
EWA-4NEB780602402-09
Pt x00
Standard
in 5F
in 5F
Hex.
Dec.
(1 digit =
0.1 5F)
> 1832.0
32767
H
1832.0
18320
H
:
:
1562.1
15621
H
1562.0
15620
H
:
:
–328.0
–3280
H
–328.1
–3281
H
:
:
–405.4
–4054
H
< – 405.4
–32768
H
Pt x00
Climatic
in 5F
in 5F
Hex.
Dec.
(1 digit =
0.01 5F)
> 311.00
32767
H
311.00
31100
H
:
:
266.01
26601
H
266.00
26600
H
:
:
–184.00
–18400
H
–184.01
–18401
H
:
:
–229.00
–22900
H
< – 229.00
–32768
H
Units
Hex.
7FFF
Overflow
H
4790
H
:
Overrange
3D05
H
3D04
H
:
Rated range
F330
H
F32F
H
:
Underrange
F02A
H
8000
Underflow
H
Units
Hex.
7FFF
Overflow
H
797C
H
:
Overrange
67E9
H
67E8
H
:
Rated range
B820
H
B81F
H
:
Underrange
A68C
H
8000
Underflow
H
Analog Electronic Modules
Range
Range
Range
Range
13-9

Advertisement

Table of Contents
loading

Table of Contents